JXB1L-63M RCBO is applicable to a line of AC 50/60Hz,rated voltage 230V, rated current to 63A to protect human electric shock , leakage protection,.The leakage breaker have overload, short circuit, over voltage protection function, It can also be used asinfrequent on-and-off operation and changeover, especially for industrial and commercial lighting distribution system.

It complies with standard IEC61009-1.

Get Quote
Basic Specification and Main Parameters

Frame class

63A

Pole number

1P+N

Standard

IEC61009-1

Rated working current(In)

6A,10A,16A ,20A,25A,32A ,40A,50A,63A

Rated working voltage(Ue)

230V

Rated frenquency

50Hz/60Hz

Rated limiting short-circuit current(Inc)

6000A

Magnetic tripping curve

C(5In~10In)

Mechanical life

4000

Electric life

2000

Rated residual operating current(I∆n)

30mA,50mA,100mA,300mA

Rated residual un-operating current(I∆no)

15mA,25mA,50mA,150mA

Rated making and breaking capacity(I∆m)

2000A

 

The Over-current Protection Property

Ambient Temperature

Initial Status

Test Current

TestTime

Expected Result

Note

30±2℃

Cold position

1.13In

t≥1h

Non-release

_

Carried out immediately after previous test

1.45In

t<1h

Release

_

Cold position

 

2.55In

1s

(In≤32A)

Release

Current smoothly rise to specified value within 5s

Cold position

2.55In

1s

(In>32A)

Release

-5~+40℃

Cold position

3In

t≥0.1s

Non-release

Type B

5In

t<0.1s

Release

Type B

Cold position

5In

t≥0.1s

Non-release

Type C

Cold position

10In

t<0.1s

Release

Type C

Cold position

10In

t≥0.1s

Non-release

Type D

Cold position

20In

t<0.1s

Release

Type D

 

Residual Current Breaking Time

In(A)

I∆n(A)

The breaking time(s) when residual current is

at the following corresponding value

I∆n

2I∆n

5I∆n

6-63

0.03

0.3

0.15

0.04

Outline & Installation Dimension

 

 

Related Products

News information

what is the difference between mcb and mccb

Both MCB and MCCB are electrical line protection devices, but they also have some differences.The difference between a molded case circuit breaker and a miniature circuit breaker is that the electrica

What is the difference between RCCB and leakage protector?

[Circuit breaker knowledge] RCCB manufacturer will introduce the difference between the residual current circuit breaker and the residual current operated circuit breaker.

Get in Touch

Captcha Code
×