JXB1-63M/PV Solar circuit breaker 3P
JXB1-63M/PV Solar circuit breaker 3P
JXB1-63M/PV Solar circuit breaker 4P

JXB1-63M/PV Solar circuit breaker

JXB1-63M/PV special DC circuit breaker is mainly used for solar photovoltaic power generation system,working voltage up to DC1000V,rated current to63A.It has overload and short circuit protection function,can quickly break the fault current of the DC distributions ystem,protect the important devices in the solar powers ystem.The PV module is protected from the reverse current on the DC side and the feedback current on the AC side caused by the fault of the inverter,ensuring the reliable operation of the solar photovoltaic power generation system.

 
Get Quote
Product characteristics

The product can realize non-polar wiring and ensure the safety of the equipment reliably.

Trip characteristics and energy consumption Overcurrent trip characteristics

Test

Type

Test Current

Initial State

Trip Or Non-trip Time Limit

Expected Result

Remark

a

c

1.05In

Cold state

t≥1h

non-trip

 

b

c

1.3In

mmediately
Carried out
after test a

t< 1h

trip

The current rises steadily to the specified value within 5s

c

c

7In

Cold state

t≥0.1s

non-trip

 

d

c

1In

Cold state

t< 0.1s

trip

 

Wiring diagram

Number of poles and width 2P(36mm) 4P(72mm)
Rated operating voltage Ue (V) DC 500 DC 1000
Rated current In (A) 6,10,16,20,25,32,40,50,63
Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp(kV) 6
Ultimate short-circuit breaking capacity Icu (kA) 6
Instantaneous trip characteristics C
Life (cycles) Mechanical 20000, electrical 1500
Use environment Ambient temperature: -25℃ to 40℃
Accessories available Auxiliary contact, alarm contact
Wiring capacity Flexible cable 25mm2 or less Hard cable 35mm2 or less
Meet the standards IEC60947-2 GB14048.2
Dimensions and installation instructions

The DC circuit breaker adopts IEC standard guide rail 35mm

 

 

Related Products

News information

what is the difference between mcb and mccb

Both MCB and MCCB are electrical line protection devices, but they also have some differences.The difference between a molded case circuit breaker and a miniature circuit breaker is that the electrica

What is the difference between RCCB and leakage protector?

[Circuit breaker knowledge] RCCB manufacturer will introduce the difference between the residual current circuit breaker and the residual current operated circuit breaker.

Get in Touch

Captcha Code
×